Relay or transistor output: which one and how to check it

Short answer: use a relay output for AC loads, for loads with their own supply or when you need isolation. Use a transistor output for DC loads that switch often or need PWM. Most output faults come from a missing output supply, a load above the rating or an inductive load without protection.

Download the checklist (PDF, 1 page)

Descarga la lista de comprobación (PDF, 1 página)

This works for any PLC or I/O module with digital outputs. At the end you will find the page for your PLC range.

The idea in one minute

A relay output is a contact. It closes a circuit that can carry AC or DC and is isolated from the PLC. It is slow, a few milliseconds, and wears out with the number of operations.

A transistor output switches DC electronically. It is fast, supports PWM and does not wear out, but it works only with DC, in one polarity, and usually needs a supply on its common.

Which one to use

NeedRelayTransistor
AC loadYesNo
DC loadYesYes, within its current rating
Fast switching or PWMNoYes
Many operations a dayWears outDoes not wear out
Isolation from the PLCThe contact is isolatedDepends on the model

Five checks when an output does not work

CheckWhat to doGood result
1. Output LEDActivate the output from the programLED on. If not, check the program or the output configuration
2. Output supplyOn transistor outputs, measure the supply on the output commonSupply present and within range
3. Voltage at the loadMeasure across the load with the output onClose to the supply voltage
4. Load currentCompare the load current with the output ratingBelow the rating of each output and of the group
5. Inductive loadsCheck the protection on coils and valvesDiode on DC loads, RC snubber or varistor on AC loads

What the readings tell you

  • LED on, no voltage at the output: no supply on the output common (transistor), or the load circuit is open (relay).
  • The output works and then stops: overload or short circuit protection. Measure the load current.
  • Relay output that stays closed: contact welded by a high inrush current. Use an interface relay or a contactor.
  • Transistor output with an AC load that does nothing: transistor outputs switch DC only.

If the output has never worked

  • On a relay output, power off the load circuit and measure continuity between the contacts with the output on and off.
  • On a transistor output, check the polarity of the load and the supply on the common.
  • Check the switches that select the output mode, where your PLC range has them.