Relay or transistor output: which one and how to check it

Short answer: as a rule of thumb, use a relay output for AC loads, for loads with their own supply or when you need isolation, and a transistor output for DC loads that switch often or need PWM, where the output supports it. When an output does not work, check the output supply, the load current, the inrush and the protection of inductive loads.

Download the checklist (PDF, 2 pages)

Descarga la lista de comprobación (PDF, 2 páginas)

This works for any PLC or I/O module with digital outputs. At the end you will find the page for your PLC range.

The idea in one minute

A relay output is a contact. It closes a circuit that can carry AC or DC and is isolated from the PLC electronics. It is slower, typically in the millisecond range, and its electrical life depends on the load: datasheets give it as a number of operations. Its DC breaking capacity is often much lower than its AC rating at the same voltage.

A transistor output switches DC electronically. It is fast, has no contact wear and supports PWM where the output is designed for it. It works only with DC, switching either the + side (PNP type) or the 0 V side (NPN type), and many transistor outputs need a supply on their common.

Which one to use

NeedRelayTransistor
AC loadYesNo
DC loadYesYes, within its current rating
Fast switching or PWM (where the output supports it)NoYes
Many operations a dayLimited electrical lifeNo contact wear
Isolation from the PLCThe contact is isolatedDepends on the model

Five checks when an output does not work

CheckWhat to doGood result
1. Output LEDActivate the output from the programLED on. On most PLCs it shows the command, not that the load is switched
2. Output supplyOn transistor outputs that need it, measure the supply on the output commonSupply present and within range
3. Voltage at the loadMeasure across the load with the output onFor a fully switched DC output, close to the load supply. PWM and AC need a suitable meter
4. Load currentCompare the load current with the output ratingBelow the rating of each output and of the group
5. Inductive loadsCheck the protection on coils and valvesA suppressor chosen for the load: typically a diode on DC coils, RC snubber or varistor on AC

What the readings tell you

  • LED on, no voltage at the output: no supply on the output common (transistor), or the load circuit is open (relay).
  • The output works and then stops: a possible cause is the output protection tripping on overload or short circuit, if the output has it. Measure the load current and the inrush.
  • Load that stays on with the output off: check first that the command is off and the wiring. On relays, contact welding from excessive inrush is one possible cause: check the inrush against the contact rating, and use a properly rated interface relay or contactor when needed.
  • Transistor output with an AC load that does nothing: transistor outputs switch DC only. Use a relay output or an AC solid-state (triac) output.

If the output has never worked

  • On a relay output, power off the load circuit and measure continuity between the contacts with the output on and off.
  • On a transistor output, check the polarity of the load and the supply on the common.
  • Check the switches that select the output mode, where your PLC range has them.