4-20 mA input reading wrong: check it step by step

Short answer: before blaming the sensor, check the loop. A 4-20 mA reading that looks wrong often comes from the wiring, the loop supply or the input configuration. Check in this order: transmitter type, loop power, loop current, input type, reference and, last, the scaling in the program. A multimeter covers most of these checks.

Download the checklist (PDF, 2 pages)

Descarga la lista de comprobación (PDF, 2 páginas)

These checks work for any PLC or I/O module with analog inputs. At the end you will find the page for your PLC range.

The idea in one minute

A 4-20 mA transmitter sets a current in the loop: 4 mA at the bottom of its range and 20 mA at the top. The current is the same at every point of the loop, so cable length and connections barely change the value, as long as the loop supply covers all the voltage drops. Because 4 mA is 0 % of the range, a reading near 0 mA points to a fault, not to a measurement.

If the PLC input measures voltage, a precision resistor turns the current into a voltage. With 500 Ω, 4 to 20 mA becomes 2 to 10 V. The resistor drops up to 10 V at 20 mA, so the loop supply must still cover the transmitter minimum voltage plus that drop.

Six checks, in order

CheckWhat to doGood result
1. Transmitter typeRead the label or datasheet: 2-wire (loop powered), 3-wire or 4-wire, and the minimum supply voltageYou know where the loop gets its power
2. Loop powerWith the loop closed, measure the voltage at the transmitter terminalsAt or above the transmitter minimum, also at 20 mA
3. Loop currentIf it is safe for the process, open the loop and measure in series with the multimeter in mA. Test terminals on the transmitter or a mA clamp meter avoid opening itBetween 4 and 20 mA, and consistent with the process
4. Input typeCheck that the input accepts current, or that it has the right resistor if it only measures voltageCurrent mode selected, or a 500 Ω precision resistor on a 0-10 V input
5. Common referenceFollow the input wiring diagram. Non-isolated single-ended inputs usually need the loop 0 V tied to the analog 0 V of the PLCConnected as the diagram shows. Isolated or differential inputs have their own requirements
6. ScalingCompare the value in the program at 4 mA and at 20 mAWith the range set to 4-20 mA, 4 mA reads as 0 % and 20 mA as 100 %

What the readings tell you

  • 0 mA or close to 0: the first suspects are an open loop, a broken wire, no loop power or reversed polarity.
  • Below 3.6 mA or above 21 mA: transmitters that follow NAMUR NE 43 use these values to signal a fault. Check the transmitter before the PLC.
  • Correct mA but wrong value in the PLC: input type, channel or scaling.
  • Reading stuck at the maximum: possible causes are a current signal on a voltage input without resistor, a wrong input range or a short circuit.
  • Value that jumps: often electrical noise. Use shielded twisted pair away from drive outputs and power cables, earth the shield as the installation specifies, and average samples if a slower response is acceptable.

If the input has never worked

  • Check the polarity: the + of the loop goes to the + of the transmitter.
  • A 2-wire transmitter needs a supply in series in the loop. Do not assume the PLC input powers it: check the datasheet.
  • Check that the program reads the right channel and the right input mode. This depends on your PLC range.