Know-How
Completed
Choosing a PLC 1: count the I/O and leave spare
166 Views •4-20 mA input reading wrong: check it step by step
329 Views •Scaling a 4-20 mA signal in the PLC: formula, constants and code
309 Views •Digital input not reading: NPN or PNP, step by step
342 Views •Relay or transistor output: which one and how to check it
266 Views •Digital input not reading: NPN or PNP, step by step
342 Views •4-20 mA input reading wrong: check it step by step
329 Views •Scaling a 4-20 mA signal in the PLC: formula, constants and code
309 Views •RS-485: how to check a bus step by step
304 Views •Relay or transistor output: which one and how to check it
266 Views •Modbus RTU timeout: 6 checks before blaming the wiring
266 Views •Upload fails: 6 checks before blaming the code
224 Views •LoRa works on the desk, fails in the field: 6 checks before you install
209 Views •SD card corrupted? 6 habits for Linux in the field
193 Views •4G PLC not connecting: 6 checks before blaming the code
188 Views •Touch panel: screen turned, touch didn't. 6 checks
178 Views •Choosing a PLC 1: count the I/O and leave spare
166 Views •Arduino IDE compile error: 6 checks before the code
166 Views •LoRaWAN node won't join: 6 checks, in order
156 Views •Choosing a PLC 2: which communications do you really need
149 Views •Node-RED not starting after a reboot? 6 checks
116 Views •Modbus RTU master and slave with two ESP32 PLC, step by step
107 Views •Modbus register 40001 or address 0? 6 checks
101 Views •PLC on Ethernet with no ping? 6 checks
88 Views •4-20 mA input reading wrong: check it step by step
Short answer: before blaming the sensor, check the loop. A 4-20 mA reading that looks wrong often comes from the wiring, the loop supply or the input configuration. Check in this order: transmitter type, loop power, loop current, input type, reference and, last, the scaling in the program. A multimeter covers most of these checks.
Download the checklist (PDF, 2 pages)
Descarga la lista de comprobación (PDF, 2 páginas)
These checks work for any PLC or I/O module with analog inputs. At the end you will find the page for your PLC range.
The idea in one minute
A 4-20 mA transmitter sets a current in the loop: 4 mA at the bottom of its range and 20 mA at the top. The current is the same at every point of the loop, so cable length and connections barely change the value, as long as the loop supply covers all the voltage drops. Because 4 mA is 0 % of the range, a reading near 0 mA points to a fault, not to a measurement.
If the PLC input measures voltage, a precision resistor turns the current into a voltage. With 500 Ω, 4 to 20 mA becomes 2 to 10 V. The resistor drops up to 10 V at 20 mA, so the loop supply must still cover the transmitter minimum voltage plus that drop.
Six checks, in order
| Check | What to do | Good result |
|---|---|---|
| 1. Transmitter type | Read the label or datasheet: 2-wire (loop powered), 3-wire or 4-wire, and the minimum supply voltage | You know where the loop gets its power |
| 2. Loop power | With the loop closed, measure the voltage at the transmitter terminals | At or above the transmitter minimum, also at 20 mA |
| 3. Loop current | If it is safe for the process, open the loop and measure in series with the multimeter in mA. Test terminals on the transmitter or a mA clamp meter avoid opening it | Between 4 and 20 mA, and consistent with the process |
| 4. Input type | Check that the input accepts current, or that it has the right resistor if it only measures voltage | Current mode selected, or a 500 Ω precision resistor on a 0-10 V input |
| 5. Common reference | Follow the input wiring diagram. Non-isolated single-ended inputs usually need the loop 0 V tied to the analog 0 V of the PLC | Connected as the diagram shows. Isolated or differential inputs have their own requirements |
| 6. Scaling | Compare the value in the program at 4 mA and at 20 mA | With the range set to 4-20 mA, 4 mA reads as 0 % and 20 mA as 100 % |
What the readings tell you
- 0 mA or close to 0: the first suspects are an open loop, a broken wire, no loop power or reversed polarity.
- Below 3.6 mA or above 21 mA: transmitters that follow NAMUR NE 43 use these values to signal a fault. Check the transmitter before the PLC.
- Correct mA but wrong value in the PLC: input type, channel or scaling.
- Reading stuck at the maximum: possible causes are a current signal on a voltage input without resistor, a wrong input range or a short circuit.
- Value that jumps: often electrical noise. Use shielded twisted pair away from drive outputs and power cables, earth the shield as the installation specifies, and average samples if a slower response is acceptable.
If the input has never worked
- Check the polarity: the + of the loop goes to the + of the transmitter.
- A 2-wire transmitter needs a supply in series in the loop. Do not assume the PLC input powers it: check the datasheet.
- Check that the program reads the right channel and the right input mode. This depends on your PLC range.