LoRa works on the desk, fails in the field: 6 checks before you install

Short answer: when a LoRa link works on the desk but loses messages in the field, check the radio settings, the antenna, the placement, RSSI and SNR at the real spot, the spreading factor, and the airtime and retries, in this order. Do it before you install.

Download the checklist (PDF, 2 pages)

Descarga la lista de comprobación (PDF, 2 páginas)

These checks apply to LoRa point to point and to LoRaWAN devices on any PLC. At the end you will find the page for your PLC range.

Six checks, in this order

CheckWhat to doGood result
1. Radio settingsIn point to point, set the same frequency, spreading factor, bandwidth, coding rate and sync word at both ends. In LoRaWAN, use the regional plan of your country and the keys registered in the network server.Both ends use exactly the same radio settings.
2. AntennaUse an antenna made for your band: 868 MHz in Europe, 915 MHz in America. Connect it before the radio transmits: transmitting without an antenna can damage the radio stage.Antenna for the right band, connected.
3. PlacementMount the antenna as high as you can, outside the metal cabinet, with a clear line of sight. Buildings, terrain and vegetation in the path reduce the range.Antenna outside and high, with a clear path to the other end.
4. Test on siteBefore you install, read RSSI and SNR at the real spot, at both ends. LoRa can receive with a negative SNR, down to a limit that depends on the spreading factor.Reliable reception with a margin above the sensitivity limit of your spreading factor.
5. Spreading factorA higher spreading factor (SF7 to SF12) reaches further, but each message takes longer on air. Use the lowest one that gives a reliable link.Reliable link with the shortest time on air.
6. Airtime and retriesIn Europe, transmit time is limited per sub-band (often 1 %). LoRa point to point has no acknowledgement: if you need confirmation, add it and retry in your application.Messages fit the airtime limit and lost ones are retried.

What the readings tell you

  • Nothing arrives, even on the desk: different radio settings at each end, or the wrong band.
  • Works on the desk, not in the field: antenna inside the cabinet, too low, or obstacles in the path.
  • RSSI and SNR close to the limit: the link works on a good day and fails on a bad one. Improve the antenna and placement, or raise the spreading factor.
  • Some messages lost: interference, a link close to the limit, or too many messages for the airtime limit. Add confirmation and retries.

On your PLC range

Sources

Radio parameters and receiver limits: Semtech SX1276/77/78/79 datasheet. Airtime limits in Europe: ERC Recommendation 70-03 and ETSI EN 300 220. Regional parameters: LoRa Alliance RP002.

LoRa link that works on the bench but not on site? Check radio settings, antenna, placement, RSSI and SNR on site, spreading factor, airtime and retries, in this order.