Modbus TCP↔RTU gateway for bioreactor control
An M-Duino exposes the whole plant over Modbus TCP and drives chillers, variable frequency drives and flow meters over RS485.
Runs on: M-Duino — Arduino sketches (.ino).
The application
A bioprocess laboratory needed to control two fermenters (temperature, agitation and flow) from its SCADA without wiring every device to the network. An M-Duino acts as a gateway: upstream it is a Modbus TCP slave (port 502) with a single register map for the whole plant; downstream it is a Modbus RTU master over RS485 driving 2 chillers, 2 variable frequency drives and 2 flow meters, plus physical I/O for sensors and pilot lights.
Architecture
- SCADA ↔ Modbus TCP (single map: coils, holding and input registers)
- M-Duino as Modbus RTU master at 9600 over half-duplex RS485
- Chillers: run command and temperature setpoint (reg. 0x06/0x0A)
- Drives: RPM setpoint (0x0144) and 32-bit actual speed reading (0x2149)
- Flow meters: 32-bit totalizer (0x100) with remote reset
Bill of materials
- M-Duino — Industrial Shields controller
- 2× thermoelectric Modbus chiller — thermal control
- 2× Modbus variable frequency drive — agitation
- 2× Modbus flow meter — accumulated litres
What is in the pack
chiller-control-rtu.inoflow-meter-reading.inogateway-modbus-tcp-rtu.inomodbus-register-map.inovfd-rpm-control.ino- Bill of materials + README
Get the pack by email — free