Communicating by MODBUS RTU through a RS485 serial interface (Seneca Z-D-in Module)

Introduction


Modbus RTU

The Modbus RTU protocol is a means of communication that allows the exchange of data between programmable logic controllers (PLCs) and computers. Electronic devices can exchange information through serial lines using the Modbus protocol.

It has been widely accepted and widely used in the construction of Building Management Systems (BMS) and Industrial Automation Systems (IAS). Its adoption has been driven by its ease of use, reliability, and the fact that it is open source and can be used without royalties on any device or application.

The protocol was developed and published by Modicon® in 1979 for use with its programmable logic controllers. It is built using a master / slave architecture and is compatible with serial devices that use the RS232 / RS485 / RS422 protocols. Modbus is often used in scenarios where multiple control and instrumentation devices transmit signals to a controller or central system to collect and analyze data. The automation and monitoring control and data acquisition (SCADA) systems often use the Modbus protocol.









What does Modbus RTU mean?

Modbus RTU (Remote Terminal Unit) is one of the two transmission modes defined in the original Modbus specification. The two modes are Modbus RTU and ASCII and are designed to be used with serial devices that support the RS232, RS485 and RS422 protocols. A distinctive feature of Modbus RTU is its use of binary encoding and strong CRC error checking. Modbus RTU is the Modbus protocol implementation that is most frequently used in industrial applications and in automated production facilities.


Requirements



Ethernet PLC or 20 I/Os industrial arduino :
Ethernet PLC
20 IOs PLC
Z-D-IN 5 Modbus RTU Module:
Visit web site
Industrial Shields boards:
How to use mapping pins on our boards
Tools40 library installed (include Modbus libraries):
Tools 40 at GitHub


Description

Z-D-In 5 Modbus RTU Module:  


The Z-D-IN Seneca Modbus RTU module is used to interface 5 digital signals (PUSH BUTTON, LIMIT SWITCH, REMOTE, CONTROL SWITCH, RELAYS, etc.) with all of control systems which are able to communicate by the protocol MODBUS RTU through the RS485 serial interface. 

A 16 bit counter is available on each input, the maximum frequency input is 100 Hz and it is possible to set one input as a fast counter with a maximum frequency of 10kHz. The module is ModBUS Slave and can be coupled with any ModBUS Master device. A 3-way galvanic isolation among Power supply // input // RS485 circuits assures the integrity of your data.








Characteristics









Power Supply10..40 Vdc; 19..28 Vac (50-60 Hz)
 








Inputs5 CH (reed, proximity, pnp, npn, contact) with common negative, self powered 24 Vdc, isolated, protected from transient up to 600 W/ms









Counters4 @ 16 bit, max frequency 100 Hz; 1 @ 32 bit, max frequency 10 KHz










Anti rebounce filterSettable from 5 to 250 ms









CommunicationRS485 a 2 fili, ModBUS RTU slave protocol










Dimensions17,5 x 100 x 112 [mm]










Mounting35 mm guide DIN 46277





The following image shows the inputs and outputs of the Z-D-IN:


Connections

 




 Final Connection: 



Software

On this sketch, we are controlling each input (5 in total) using digital switches. The communication between the PLC Arduino and the Z-D-in Modbus RTU module is by RS485 in half duplex, so it's very important that you download and use the RS485.h library as well as the ModbusRTUSlave.h library to work on this protocol.

The Z-D-in module acts as a slave and the controller Arduino will act as the master of the system.

In this sketch, requests for reading the entries are sent every second and changes are shown on the screen. Each entry has associated a counter that will increment for each change that can be read in the entry.

The full sketch is shown below:

/*

   Copyright (c) 2019 Boot&Work Corp., S.L. All rights reserved

   This program is free software: you can redistribute it and/or modify

   it under the terms of the GNU Lesser General Public License as published by

   the Free Software Foundation, either version 3 of the License, or

   (at your option) any later version.

   This program is distributed in the hope that it will be useful,

   but WITHOUT ANY WARRANTY; without even the implied warranty of

   MERCHANTABILITY or FITNESS FOR A PARTICULAR PURPOSE.  See the

   GNU Lesser General Public License for more details.

   You should have received a copy of the GNU Lesser General Public License

   along with this program.  If not, see <http://www.gnu.org/licenses/>.

*/


#include <ModbusRTUMaster.h>

#include <RS485.h>


const uint8_t slaveAddress = 1;

const uint32_t serialRate = 38400UL;

const int serialConfig = SERIAL_8N1;

const uint32_t requestPeriod = 1000UL; // ms

const int numInputs = 5;


ModbusRTUMaster modbus(RS485);


uint8_t inputStates[numInputs];

uint16_t inputCounters[numInputs];


////////////////////////////////////////////////////////////////////////////////////////////////////

void setup() {

  Serial.begin(9600L);

  Serial.println("seneca-z-d-in-module started");

  RS485.begin(serialRate, HALFDUPLEX, serialConfig);

  modbus.begin(serialRate);

}


////////////////////////////////////////////////////////////////////////////////////////////////////

void loop() {

  static uint32_t lastRequestTime = millis();

  // Send a request every 1000ms

  if (!modbus.isWaitingResponse()) {

    if (millis() - lastRequestTime > requestPeriod) {

      // Send a Read Holding Registers request to the slave with address 1

      // IMPORTANT: all read and write functions start a Modbus transmission, but they are not

      // blocking, so you can continue the program while the Modbus functions work. To check for

      // available responses, call modbus.available() function often.

      if (!modbus.readHoldingRegisters(slaveAddress, 1, 6)) {

        // TODO Failure treatment

      }

      lastRequestTime = millis();

    }

  }


  // Check available responses often

  ModbusResponse response = modbus.available();

  if (response) {

    if (response.hasError()) {

      // TODO Response failure treatment. You can use response.getErrorCode()

      // to get the error code.

    } else {

      uint16_t states = response.getRegister(0);

      for (int i = 0; i < numInputs; ++i) {

        inputStates[i] = (states >> i) & 0x01;

        inputCounters[i] = response.getRegister(i + 1);

      }

      printInputs();

    }

  }

}


////////////////////////////////////////////////////////////////////////////////////////////////////

void printInputs() {

  Serial.println();

  Serial.print("Inputs: ");

  for (int i = 0; i < numInputs; ++i) {

    Serial.print(inputStates[i] ? "HIGH" : "LOW ");

    Serial.print(' ');

  }

  Serial.println();

  Serial.print("Counters: ");

  for (int i = 0; i < numInputs; ++i) {

    Serial.print(inputCounters[i]);

    Serial.print(' ');

  }

  Serial.println();

}

Do you want more information?